Cable Size Calculator

Calculate the correct cable cross-section (mm²) for any electrical load — based on IS 1554 / IS 732 standards.

Enter Load Details

Enter load, voltage and cable length to get your result.

Formula Used
I = P / (√3 × V × PF) ← 3-phase FLC
I = P / (V × PF) ← 1-phase FLC
A = (√3 × L × I × ρ) / ΔV ← VD sizing
ρ(Cu) = 0.0175 Ω·mm²/m | ρ(Al) = 0.028 Ω·mm²/m

IS 1554 Current Carrying Capacity Reference

Ampere ratings at 30°C ambient, 90°C conductor temperature

Size (mm²)Cu UndergroundAl UndergroundCu In AirAl In Air
1.5 mm²27 A21 A18 A14 A
2.5 mm²36 A28 A25 A19 A
4 mm²48 A37 A33 A26 A
6 mm²62 A48 A43 A33 A
10 mm²85 A65 A58 A45 A
16 mm²112 A87 A78 A60 A
25 mm²141 A109 A100 A77 A
35 mm²173 A133 A122 A94 A
50 mm²210 A162 A149 A115 A
70 mm²258 A199 A189 A146 A
95 mm²310 A239 A229 A177 A
120 mm²358 A276 A263 A203 A
150 mm²407 A314 A302 A233 A
185 mm²464 A358 A345 A266 A
240 mm²541 A416 A407 A314 A
300 mm²621 A479 A468 A361 A
Disclaimer: This calculator provides indicative cable sizing based on IS 1554 and IS 732 standards under standard conditions. Results must be verified by a licensed electrical engineer before use in actual installations. Derating factors for ambient temperature, grouping, and soil thermal resistivity may apply. KVP Electricals Pvt Ltd accepts no liability for decisions made solely on the basis of this tool.